Lenovo 0U Basic PDUs Product Guide

Lenovo 0U Basic PDUs Product Guide

Le pdf se trouve ci-dessous. Vous pouvez télécharger le pdf en cliquant à droite.

Revenir à l'accueil

 

Abstract

The Lenovo zero-U (0U) Basic power distribution units (PDUs) are the ideal solutions when you need flexible, reliable, easy-to-deploy power distribution with branch circuit protection to minimize downtime. These rack-dense units distribute power to up to 42 outlets. The 0U PDUs are designed to be installed vertically in the rear channel or side pockets of a Lenovo rack, thereby not consuming any horizontal rack space.

This product guide provides essential presales information to understand the 0U Basic PDUs and their key features, specifications, and compatibility. This guide is intended for technical specialists, sales specialists, sales engineers, IT architects, and other IT professionals who want to learn more about 0U Basic PDUs and consider their use in IT solutions.

Change History

Changes in the April 2 update:

Introduction

The Lenovo zero-U (0U) Basic power distribution units (PDUs) are the ideal solutions when you need flexible, reliable, easy-to-deploy power distribution with branch circuit protection to minimize downtime. These rack-dense units distribute power to up to 42 outlets. The 0U PDUs are designed to be installed vertically in the rear channel or side pockets of a Lenovo rack, thereby not consuming any horizontal rack space that otherwise be used by servers, storage and network switches (hence the term 0U).

The following figure displays the 0U Basic PDUs.

Lenovo 0U Basic PDUs
Figure 1. Lenovo 0U Basic PDUs

Did you know?

With ever growing power densities in today’s rack environments, it is all too easy to add load in the wrong place and trigger an overload event. The 0U Basic PDU offerings can minimize this impact, providing the ability to quickly recover with resettable circuit breakers for each designated bank of receptacles, referred to as load groups. Breakers are color coded to the receptacles in a particular load group to aid in configuration, installation, and maintenance.

Introduction to PDUs

A power distribution unit (PDU) is a highly reliable, multiple outlet power strip designed to consolidate line cords within the rack and distribute conditioned power from an uninterruptible power supply (UPS) or utility power to servers and other IT equipment. The PDU efficiently distributes power within the rack and provides fault-tolerant power redundancy for high availability requirements.

There are three types of PDUs available from Lenovo: basic, monitored, and switched & monitored. The PDUs covered in this document are of the basic type.

Part number information

The following table provides the ordering part numbers and feature codes for the 0U Basic PDUs.

Table 1. Ordering part numbers and feature codes
Part
number
Feature
code
Description Region
availability*
00YJ776 ATZY 0U 36 C13/6 C19 24A 1 Phase PDU (30A derated) North America
00YJ777 ATZZ 0U 36 C13/6 C19 32A 1 Phase PDU International
00YJ778 AU00 0U 21 C13/12 C19 32A 3 Phase PDU International
00YJ779 ATZX 0U 21 C13/12 C19 48A 3 Phase PDU (60A derated) North America

* See region availability below

Region availability

PDUs indicated in Table 1 as available for North America are available in the following countries:

PDUs indicated in Table 1 as available Internationally are available in these regions:

Included with the PDUs

The PDUs include the following items:

Features and specifications

The 0U Basic PDUs have the following common features:

The following table compares the technical and environmental specifications of the 0U Basic PDUs.

Table 2. PDU specifications
Feature 0U 36 C13/6 C19 30A 1 Phase PDU 0U 36 C13/6 C19 32A 1 Phase PDU 0U 21 C13/12 C19 32A 3 Phase PDU 0U 21 C13/12 C19 60A 3 Phase PDU
Part Number 00YJ776 00YJ777 00YJ778 00YJ779
Feature Code ATZY ATZZ AU00 ATZX
Region North America International International North America
Input power
Number of phases Single phase input Three phase input
Line cord Attached line cord, 3 m length (9-ft, 10-in)
Line cord connector NEMA L6-30P 332P6, W+N+PE 1ph 532P6, WYE, 3W+N+PE 3Ph HBL460P9, Delta 3W+PE 3ph
Plug design
Input voltage 200-240V 200-240V 200-240V / 350-415V 200-240V
Input current 24A (derated from 30A) 32A 32A 48A (derated from 60A)
Maximum power rating 5760 VA 7680 VA 23,040 VA 20,736 VA
Output power
Number of C13 outlets 36 36 21 21
Number of C19 outlets 6 6 12 12
Output voltage rating at 50/60Hz 200-240V 200-240V 200-240V 200-240V
Output current rating Each C13 outlet: 10 amps; Each C19 outlet: 16 amps
Circuit breakers Two double-pole branch rated circuit breakers rated at 16A Six double-pole branch rated circuit breakers rated at 16A
Number of load groups 2 (A, B) 2 (A, B) 6 (A-F) 6 (A-F)
Number of outlets per load group A = 18x C13, 3x C19
B = 18x C13, 3x C19
A = 18x C13, 3x C19
B = 18x C13, 3x C19
A = 4x C13, 2x C19
B = 4x C13, 2x C19
C = 4x C13, 2x C19
D = 3x C13, 2x C19
E = 3x C13, 2x C19
F = 3x C13, 2x C19
A = 4x C13, 2x C19
B = 4x C13, 2x C19
C = 4x C13, 2x C19
D = 3x C13, 2x C19
E = 3x C13, 2x C19
F = 3x C13, 2x C19
Capacity per load group (Amps) A = 20 A
B = 20 A
A = 16 A
B = 16 A
A = 20 A
B = 20 A
C = 20 A
D = 16 A
E = 16 A
F = 16 A
A = 20 A
B = 20 A
C = 20 A
D = 20 A
E = 20 A
F = 20 A
Capacity per phase (Amps) Not applicable Not applicable Phase 1:
A + D = 32 A
Phase 2:
B + E = 32 A
Phase 3:
C + F = 32 A
Phase 1:
A + D = 32 A
Phase 2:
B + E = 32 A
Phase 3:
C + F = 32 A
Capacity per PDU (Amps) 24 A 32 A 96 A 86 A
Mechanical and environmental
Physical dimensions (DxWxH) 2.5 x 2.0 x 66.4 in
66 x 52 x 1689 mm
2.5 x 2.0 x 66.4 in
66 x 52 x 1689 mm
3.0 x 2.0 x 66.4 in
77 x 52 x 1689 mm
3.8 x 2.0 x 66.4 in
99 x 52 x 1689 mm
Weight 4 kg / 8.8 lb. 4 kg / 8.8 lb. 5.3 kg / 11.6 lb. 8.7 kg / 19.1 lb.
Operating temperature 10° C to 55° C
50° F - 122° F
10° C to 60° C
50° F to 140° F
10° C to 60° C
50° F to 140° F
10° C to 55° C
50° F - 122° F
Operating humidity 5% to 95% without condensation

Connectors and load groups

The 0U Basic PDUs with 36 C13 connectors and 6 C19 connectors (part numbers 00YJ776 and
00YJ777) have the components and controls as shown in the following figure.

Load groups for 00YJ776 and 00YJ777
Figure 2. Load groups for part numbers 00YJ776 and 00YJ777

The 0U Basic PDUs with 21 C13 connectors and 12 C19 connectors (part numbers 00YJ778 and 00YJ779) have the components and controls as shown in the following figure.

Load groups for part numbers 00YJ778 and 00YJ779
Figure 3. Load groups for part numbers 00YJ778 and 00YJ779

Selecting the right PDU

To avoid over sizing or under sizing power, it is important to understand the power requirements of the hardware that will be powered by the PDU(s). To understand this, use the Power Configurator tool to determine the hardware’s overall power usage. Download the Power Configurator from the following link: http://support.lenovo.com/au/en/documents/LNVO-PWRCONF

Likewise, to avoid over sizing or under sizing PDUs it is also important to understand the PDU capabilities and capacities.

Consider the following for capabilities:

Consider the following for capacities:

For additional information on selecting the right PDU, load groups, phases, outlets, line cords, plugs and specifications, see the Lenovo PDU Technical Reference (International or North American version), available from: http://support.lenovo.com/documents/lnvo-powinf

Supported rack cabinets

The 0U Basic PDUs can be installed in the following racks:

Each PDU has a universal mounting bracket that enables the PDU to be mounted in a variety of different racks that are outside of the Lenovo portfolio.

The PDU is designed to be mounted without the use of tools. Mounting buttons are pre-installed on the rear of the PDU at the factory. The mounting buttons allow for three mounting methods for installing the 0U Basic PDUs vertically in a rack.

For additional information on racking the 0U Basic PDUs, refer to User’s Guide for the PDUs.

Warranty

The 0U Basic PDUs are offered with a three-year limited warranty. At Lenovo discretion this warranty will be either CRU service (customer replaceable unit) or a Lenovo employee, subcontractor or reseller will be assigned to repair the failing item. Proof and date of purchase is required for warranty claims.

Agency approvals

The PDUs conform to the following standards:

Related product families

Product families related to this document are the following: